| Element | RTD : Pt 100 Ω at 0 °C(DIN) Film type | 
| Body material | Coil End Temperature Detector : Teflon Bearing Temperature Sensor : 304SS, 316SS, 316L SS
 | 
| Body outer diameter and length | Coil End Temperature Detector : Min. 4 x Min. 25 mm Bearing Temperature Sensor : Min. 3.2 x Min. 6.35 mm
 | 
| Molding | Coil End Temperature Detector : Silicone filled Bearing Temperature Sensor : Epoxy filled, Silicon filled
 | 
| Standard | Explosive atmospheres. Equipment - General requirements
 IEC 60079-0 / EN 60079-0
 Electrical apparatus for explosive gas atmospheres.
 Increased safety " e "
 IEC 60079-7 / EN 60079-7
 Intrinsic safety " i "
 IEC 60079-11 / EN 60079-11
 | 
| Certificates | ATEX II 2G Ex e IIC Gb IECEx Ex e IIC Gb
 ATEX II 1G Ex ia IIC T6...T3 Ga
 IECEx Ex ia IIC T6...T3 Ga
 | 
| Tolerances on temperature reading | R.T.D. Class A : ± (0.15 + 0.002 l t l)
 Class B : ± (0.3 + 0.005 l t l)
 | 
| Service Temperature (Ex e) | -40 °C ≤ Tservice ≤ 180 °C | 
| Ambient Temperature | ■ Temperature class T6 : -40 °C < Tamb < 75 °C (1) One Pt100
 Ui = 30 V, Ii = 25 mA, Pi = 70 mW
 (2) Two Pt100
 Ui = 30 V, Ii = 15 mA (each Pt100),
 Pi = 50 mW (together)
 ■ Temperature class T5 : -40 °C < Tamb < 95 °C
 (1) One Pt100
 Ui = 30 V, Ii = 55 mA, Pi = 630 mW
 (2) Two Pt100
 Ui = 30 V, Ii = 45 mA (each Pt100),
 Pi = 760 mW (together)
 ■ Temperature class T4 : -40 °C < Tamb < 130 °C
 (1) One Pt100
 Ui = 30 V, Ii = 55 mA, Pi = 630 mW
 (2) Two Pt100
 Ui = 30 V, Ii = 50 mA (each Pt100),
 Pi = 1 W (together)
 ■ Temperature class T3 : -40 °C < Tamb < 180 °C
 (1) One Pt100
 Ui = 30 V, Ii = 40 mA, Pi = 255 mW
 (2) Two Pt100
 Ui = 30 V, Ii = 30 mA (each Pt100),
 Pi = 260 mW (together)
 | 
| Hersteller |  |